在(zai)通(tong)信網(wang)絡(luo)高速發(fa)展,通信電(dian)源(yuan)系(xi)統(tong)作為保(bao)障基站、數據(ju)中心、工業(ye)互聯網(wang)等(deng)場(chang)景穩(wen)定(ding)運(yun)行的“心臟”,其(qi)可靠性直接(jie)關(guan)系(xi)到業務連(lian)續性。然(ran)而(er),電(dian)源(yuan)系(xi)統(tong)結(jie)構復(fu)雜(涉(she)及輸(shu)入(ru)源、配(pei)電(dian)單(dan)元、整流模塊、蓄電(dian)池(chi)、控制電(dian)路(lu)等(deng)環節(jie)),壹旦出現故障(zhang),快速(su)定(ding)位(wei)損(sun)壞位(wei)置(zhi)成(cheng)為運(yun)維(wei)人(ren)員(yuan)的核心挑戰(zhan)。本文(wen)結(jie)合深圳市(shi)華(hua)強偉(wei)業電(dian)源(yuan)技(ji)術(shu)有(you)限(xian)公(gong)司(si)電(dian)源(yuan)研發經驗(yan),總(zong)結(jie)出壹套分層排(pai)查、工具(ju)輔(fu)助、安(an)全規(gui)範(fan)的故障(zhang)定(ding)位(wei)方法,助(zhu)您高(gao)效(xiao)解決電(dian)源(yuan)系(xi)統(tong)問(wen)題。
判斷通信電(dian)源(yuan)系(xi)統(tong)損(sun)壞位(wei)置(zhi),可(ke)按以(yi)下邏(luo)輯(ji)排(pai)查,結(jie)合輸入源、配(pei)電(dian)單(dan)元、整流模塊、蓄電(dian)池(chi)、控制電(dian)路(lu)等(deng)關(guan)鍵環節(jie)定(ding)位(wei)故障(zhang):
壹、輸入源檢(jian)查:確認供(gong)電(dian)基礎是(shi)否正常
1.市(shi)電(dian)輸(shu)入檢(jian)測(ce)
用萬(wan)用表(biao)測(ce)量交(jiao)流輸入電(dian)壓(ya),確認是(shi)否在(zai)正常範(fan)圍(如160-280Vac)。若(ruo)電(dian)壓(ya)異常(過(guo)高/過(guo)低(di)/缺(que)相(xiang)),需(xu)排(pai)查外(wai)部(bu)電(dian)網(wang)或(huo)線路(lu)問(wen)題。
檢(jian)查交(jiao)流接觸器(qi)是(shi)否吸合:若(ruo)接(jie)觸(chu)器(qi)不吸合,可(ke)能是(shi)線圈供(gong)電(dian)保(bao)險(xian)絲(si)燒(shao)壞、輔(fu)助接(jie)觸器(qi)損壞或(huo)控制板故障(zhang)。
2.防(fang)雷器(qi)狀態(tai)檢(jian)查
觀(guan)察防(fang)雷器(qi)窗口(kou)顏色:綠色為正常,紅(hong)色表示(shi)損壞需更(geng)換。
若(ruo)防(fang)雷器(qi)未損壞但(dan)監控告(gao)警,檢(jian)查接(jie)觸是(shi)否良(liang)好,可拔插重試(shi)。
二(er)、配(pei)電(dian)單(dan)元排(pai)查:定(ding)位(wei)分(fen)配(pei)環節(jie)故障(zhang)
1.交(jiao)流配(pei)電(dian)故障(zhang)
若交(jiao)流變送(song)器(qi)報缺(que)相(xiang)但(dan)實際供(gong)電(dian)正常,用萬(wan)用表(biao)測(ce)量變送(song)器(qi)端子(zi)電(dian)壓(ya)(應為3V左(zuo)右直流),若無(wu)電(dian)壓(ya)則需更(geng)換變送(song)器(qi)。
檢(jian)查交(jiao)流斷路(lu)器(qi)是(shi)否跳(tiao)閘:若(ruo)跳(tiao)閘且(qie)無(wu)短路(lu),可(ke)能是(shi)過(guo)載(zai)或(huo)漏(lou)電(dian)保(bao)護(hu)動作。
2.直流配(pei)電(dian)故障(zhang)
負載(zai)開關(guan)頻跳(tiao)閘:檢(jian)查負(fu)載(zai)是(shi)否短(duan)路(lu)或(huo)過(guo)載(zai),用萬(wan)用表(biao)測(ce)量輸(shu)出(chu)端電(dian)阻(zu)(正常應(ying)為非(fei)零值(zhi))。
電(dian)池(chi)熔絲(si)熔斷:檢(jian)查蓄(xu)電(dian)池(chi)組是(shi)否短(duan)路(lu)(如(ru)內(nei)部(bu)極(ji)板(ban)硫(liu)化(hua)、電(dian)解(jie)液泄漏(lou)),用萬(wan)用表(biao)測(ce)量電(dian)池(chi)組電(dian)壓(ya)是(shi)否正常。
三、整流模塊分析:核心轉(zhuan)換(huan)環節(jie)故障(zhang)
1.無(wu)輸出(chu)或(huo)輸出異(yi)常
無(wu)輸出(chu):檢(jian)查交(jiao)流輸入開關(guan)是(shi)否合(he)上、輸(shu)入熔(rong)絲(si)是(shi)否熔(rong)斷;若模(mo)塊(kuai)指(zhi)示(shi)燈不亮(liang),可(ke)能是(shi)模(mo)塊故障(zhang),需更(geng)換。
輸(shu)出電(dian)壓(ya)過(guo)高/過(guo)低(di):
過(guo)高:檢(jian)查穩(wen)壓取(qu)樣電(dian)路(lu)(如(ru)取(qu)樣電(dian)阻(zu)、TL431誤(wu)差放(fang)大(da)器(qi)、光(guang)電(dian)耦(ou)合器(qi))是(shi)否損(sun)壞。
過(guo)低(di):檢(jian)查開關(guan)管(guan)是(shi)否性能下降、開關(guan)變壓(ya)器(qi)是(shi)否不(bu)良(liang)、大(da)濾(lv)波(bo)電(dian)容(rong)是(shi)否失(shi)效(xiao)(用代(dai)換(huan)法判斷)。
2.過(guo)熱(re)或(huo)風扇故障(zhang)
若模(mo)塊(kuai)溫(wen)度超(chao)過(guo)85℃自(zi)動(dong)停(ting)機(ji),檢(jian)查風(feng)扇是(shi)否堵(du)塞或(huo)老化,清(qing)理(li)灰(hui)塵(chen)或(huo)更(geng)換風(feng)扇。
若風(feng)扇不轉(zhuan),檢(jian)查風(feng)扇控制電(dian)路(lu)或(huo)電(dian)機(ji)是(shi)否損(sun)壞。
四(si)、蓄電(dian)池(chi)組檢(jian)測(ce):儲能環節(jie)故障(zhang)
1.外(wai)觀(guan)與(yu)電(dian)壓(ya)檢(jian)查
檢(jian)查電(dian)池(chi)殼體是(shi)否滲(shen)液(ye)、鼓(gu)脹(zhang)變形(xing)(可(ke)能是(shi)過(guo)充或(huo)制造缺(que)陷導致(zhi)熱(re)失(shi)控(kong))。
用萬(wan)用表(biao)測(ce)量電(dian)池(chi)組總(zong)電(dian)壓(ya)和(he)單(dan)體電(dian)壓(ya),若電(dian)壓(ya)異常低(di),可(ke)能是(shi)電(dian)池(chi)老化(hua)或(huo)內(nei)部(bu)短(duan)路(lu)。
2.內(nei)阻(zu)與(yu)容(rong)量(liang)測(ce)試(shi)
用內(nei)阻(zu)測(ce)試(shi)儀(yi)測(ce)量電(dian)池(chi)內(nei)阻(zu),若內(nei)阻(zu)顯著增大(da)(超(chao)過(guo)標稱(cheng)值(zhi)50%),需更(geng)換電(dian)池(chi)。
進行放(fang)電(dian)測(ce)試(shi),若(ruo)實際容(rong)量(liang)低(di)於(yu)額(e)定(ding)容(rong)量(liang)80%,表明電(dian)池(chi)壽(shou)命(ming)終(zhong)結(jie)。
五、控制電(dian)路(lu)診(zhen)斷:智能管(guan)理(li)環節(jie)故障(zhang)
1.監控系(xi)統(tong)告(gao)警
若監控單(dan)元報“通(tong)信錯(cuo)誤(wu)”,檢(jian)查通(tong)信線路(lu)是(shi)否松(song)動、接(jie)口(kou)是(shi)否氧(yang)化,或(huo)更(geng)換通(tong)信模塊(kuai)。
若報(bao)“控制失(shi)效(xiao)”,檢(jian)查控(kong)制芯(xin)片(pian)(如TL494)各引(yin)腳(jiao)電(dian)壓(ya)是(shi)否正常,用示(shi)波(bo)器(qi)觀察驅(qu)動(dong)信號是(shi)否跳(tiao)變。
2.保(bao)護(hu)功(gong)能誤(wu)動作
若(ruo)頻(pin)繁報“過(guo)壓/過(guo)流/欠(qian)壓(ya)”保(bao)護(hu),檢(jian)查保(bao)護(hu)電(dian)路(lu)元器(qi)件(如(ru)壓敏(min)電(dian)阻(zu)、氣體放(fang)電(dian)管(guan))是(shi)否老(lao)化或(huo)選型不當(dang)。
若保(bao)護(hu)功(gong)能失(shi)效(xiao),可能是(shi)接(jie)地不良(liang)導(dao)致能量無(wu)法泄(xie)放(fang),需(xu)檢(jian)查接(jie)地系(xi)統(tong)。
六(liu)、線路(lu)與(yu)連(lian)接件(jian)排(pai)查:隱(yin)蔽環節(jie)故障(zhang)
1.線路(lu)老(lao)化或(huo)破損
檢(jian)查電(dian)源(yuan)線絕緣(yuan)皮是(shi)否破(po)損、接(jie)頭是(shi)否松(song)動氧(yang)化(用紅(hong)外(wai)測(ce)溫(wen)儀(yi)檢(jian)測(ce)連(lian)接點溫(wen)度)。
若線路(lu)被(bei)鼠(shu)咬或(huo)擠壓變形(xing),需(xu)更(geng)換線路(lu)並(bing)加(jia)強防(fang)護(hu)。
2.接觸不(bu)良(liang)或(huo)虛(xu)焊
對可疑連(lian)接點(如整流橋(qiao)、開關(guan)管(guan)引(yin)腳(jiao))進(jin)行重新焊接,用萬(wan)用表(biao)測(ce)量接(jie)觸(chu)電(dian)阻(zu)(應小(xiao)於(yu)0.1Ω)。
總(zong)結(jie):故障(zhang)排(pai)除邏(luo)輯(ji)與(yu)工具(ju)
分層(ceng)排(pai)查:按(an)“輸入源→配(pei)電(dian)單(dan)元→整流模塊→蓄電(dian)池(chi)→控制電(dian)路(lu)”順(shun)序逐步縮(suo)小範圍(wei)。
關(guan)鍵工具(ju):萬用表(biao)(測(ce)電(dian)壓(ya)/電(dian)阻(zu))、示(shi)波(bo)器(qi)(測(ce)信號波(bo)形(xing))、內(nei)阻(zu)測(ce)試(shi)儀(yi)(測(ce)電(dian)池(chi))、紅外(wai)測(ce)溫(wen)儀(yi)(測(ce)溫(wen)度)。
安(an)全規(gui)範(fan):帶電(dian)操(cao)作時(shi)需(xu)佩(pei)戴絕緣(yuan)手(shou)套,避免短(duan)路(lu)或(huo)觸電(dian);更(geng)換模(mo)塊前(qian)需斷開電(dian)源(yuan)。
通過(guo)以(yi)上方法,可(ke)快(kuai)速定(ding)位(wei)通(tong)信電(dian)源(yuan)系(xi)統(tong)故障(zhang)點,並結(jie)合設(she)備手(shou)冊進(jin)行針對性維(wei)修或(huo)更(geng)換。
深(shen)圳市(shi)華(hua)強偉(wei)業電(dian)源(yuan)技(ji)術(shu)有(you)限(xian)公(gong)司(si)深耕通(tong)信電(dian)源(yuan)領域,提供從設(she)計(ji)、生產(chan)到運維(wei)的全生(sheng)命(ming)周(zhou)期(qi)解(jie)決方案。如(ru)需(xu)進壹步技(ji)術(shu)咨詢(xun)或(huo)定(ding)制化服務,歡迎(ying)聯系(xi)我們(men):0755-29364858,或(huo)訪問官(guan)網(wang)http://vrdw.cn//獲(huo)取(qu)更(geng)多資料(liao)。